title: "30-minute safety cabinets"
description: "Renggli 30 minute fire safety cabinets for flammable liquids to EN 14470-1, with automatic door closing and a ventilation connection, in the Q, S and K series."
canonical_url: "https://www.renggli.pl/en/offer/safety-storage-cabinets/specialized-safety-cabinets-30m"
language: "en"
alternates:
  pl: "https://www.renggli.pl/pl/oferta/szafy-ognioodporne/szafy-specjalistyczne-30m.md"
  de: "https://www.renggli.pl/de/angebot/sicherheitsschraenke/spezial-sicherheitsschraenke-30m.md"
  uk: "https://www.renggli.pl/uk/propozycja/spetsializovani-shafy/shafy-bezpeky-30-khv.md"
  lt: "https://www.renggli.pl/lt/pasiulymas/specializuoti-saugumo-spintos/specializuotos-saugos-spintos-30m.md"
---

# 30-minute safety cabinets

> Renggli 30 minute fire safety cabinets for flammable liquids to EN 14470-1, with automatic door closing and a ventilation connection, in the Q, S and K series.

![Double-door fire-resistant chemical cabinet in a laboratory](https://www.renggli.pl/m/szafy-laboratoryjne-rozszerzone-5x4__h1560f.webp)

Type 30 fire-resistant safety storage cabinets are classed as type 30 under EN 14470-1: in a fire, their insulated body and self-closing doors keep the flammable liquids inside the compartment isolated from the flames for 30 minutes. The range covers three series, Q-Classic-30, K-Phoenix-30 and S-Phoenix-30, in widths from 564 to 1202 mm, each with a connection for air extraction.

## What type 30 means under EN 14470-1 {#what-type-30-means-under-en-14470-1}

Type 30 means that, in a fire, the cabinet shields its contents from the rising temperature outside for 30 minutes. The number in the designation gives the protection time in minutes. It says nothing about the cabinet's capacity or the material it is made from. The protection comes from the whole construction: a multi-layer body filled with insulation, self-closing doors, intumescent seals that expand at high temperature and shut-off dampers in the ventilation connection. Once a temperature threshold is exceeded, a mechanism releases the door hold-open and the doors close. If the temperature keeps rising, the dampers close and the seals swell to fill the gaps. All of this works without power and without anyone having to act. Our article on how to [choose a cabinet's fire resistance class](https://www.renggli.pl/en/blog/laboratory-cabinet-markings-fire-resistance-class) explains how to read the markings on the rating plate and in the technical data sheet.

## When a 30-minute fire-resistant cabinet is enough {#when-a-30-minute-fire-resistant-cabinet-is-enough}

A 30-minute fire-resistant safety storage cabinet is sufficient where smaller quantities of flammable liquids are stored. The choice of class depends on the substances' safety data sheets and the quantities kept. A longer protection time gives more minutes for evacuation and more time for the fire service, which is why larger stocks of solvents call for [type 90 fire-resistant safety storage cabinets](https://www.renggli.pl/en/offer/safety-storge-cabinets/specialized-safety-cabinets-90m). Cabinets of any type are placed away from the main escape routes, so their position is best decided together with the rest of the furniture layout. We cover this in our guide on how to [plan storage in the laboratory](https://www.renggli.pl/en/blog/laboratory-cabinets-how-to-plan-storage). Acids and alkalis that are not flammable belong in [chemical storage cabinets](https://www.renggli.pl/en/offer/safety-storge-cabinets/chemical-storage-cabinets), because what matters for them is an interior that resists fumes, not a fire rating. We have set out their requirements in the article [cabinets for acids and alkalis](https://www.renggli.pl/en/blog/acid-and-base-cabinet-requirements). Other cabinet types are in the category [fire-resistant and safety cabinets](https://www.renggli.pl/en/offer/safety-storge-cabinets).

## Q-Classic-30, K-Phoenix-30 and S-Phoenix-30 models {#q-classic-30-k-phoenix-30-and-s-phoenix-30-models}

All three series offer 30 minutes of fire resistance to EN 14470-1 and have a cylinder lock. They differ in their doors, width and interior.

- [Q-Classic-30 fire-resistant cabinet](https://www.renggli.pl/en/offer/safety-storge-cabinets/specialized-safety-cabinets-30m/q-classic-30): width 564, 864 or 1164 mm, height 1947 mm. The doors close automatically in a fire and can be held open in set positions. A spill sump sits at the bottom, and built-in air ducts lead to the ventilation connection.
- [K-Phoenix-30 fire-resistant cabinet](https://www.renggli.pl/en/offer/safety-storge-cabinets/specialized-safety-cabinets-30m/k-phoenix-30): width 1202 mm, height 1968 mm. It holds flammable liquids and other hazardous chemicals in a single cabinet. It has an absorbent insert for spills of two types of substance and levelling feet for uneven floors. The protective components are mounted outside the compartment, which improves corrosion resistance.
- [S-Phoenix-30 fire-resistant cabinet](https://www.renggli.pl/en/offer/safety-storge-cabinets/specialized-safety-cabinets-30m/s-phoenix-30): width 600, 900 or 1200 mm, height 1968 mm. Folding doors take up less space in front of the cabinet, and the lock can be integrated into a central locking system. Height-adjustable shelves carry up to 75 kg, and the spill sump at the bottom takes large containers.

## Ventilation connection and minimum air extraction {#ventilation-connection-and-minimum-air-extraction}

A 30-minute cabinet can be connected to an extraction system through the connection in its body. The model data sheets give the minimum air extraction based on 10 air changes per hour. For the Q-Classic-30 this is 9 m³/h at a width of 1164 mm, 6 m³/h at 864 mm and 4 m³/h at 564 mm; for the K-Phoenix-30 it is 9 m³/h. Extraction removes vapours from the compartment, which escape even from properly closed bottles. In a fire, the dampers in the connection close automatically, so hot gases cannot enter the compartment through the duct. The criteria for choosing a cabinet with permanent extraction when vapours are toxic or corrosive are covered in our article on [when you need a ventilated cabinet](https://www.renggli.pl/en/blog/ventilated-chemical-cabinet-when-is-it-needed).

## Products

- [Fire-resistant safety cabinet K-Phoenix-30](https://www.renggli.pl/en/offer/safety-storage-cabinets/specialized-safety-cabinets-30m/k-phoenix-30): K Series
- [Fire-resistant safety cabinet Q-Classic-30](https://www.renggli.pl/en/offer/safety-storage-cabinets/specialized-safety-cabinets-30m/q-classic-30): Q Series
- [Fire-resistant safety cabinet S-Phoenix-30](https://www.renggli.pl/en/offer/safety-storage-cabinets/specialized-safety-cabinets-30m/s-phoenix-30): S Series

## Additional information common to all cabinets

- **Safety and durability:** Robust construction and durability; Safety elements mounted outside the chamber to increase protection against corrosion; Doors equipped with a cylinder lock and a closure status indicator (red/green)
- **Standards and certificates:** All cabinets are fire-resistant in accordance with EN 14470-1 standard. It is possible to combine various functionalities within a single product. The cabinet can be resistant to both corrosive and toxic substances. All models offered by us are made of high-quality durable steel and are equipped with ventilation openings.
- **Fire-resistant cabinets** Although the primary purpose of the cabinets is to ensure safety in the event of a fire, a major advantage of the cabinets is also their high resistance to mechanical damage and the lockable doors. Thanks to these features of our safety cabinets, you can be sure that the materials you store are not only kept in safe conditions but also that unauthorized persons will not have access to them.

## Questions about 30-minute fire-resistant cabinets

**How does a 30-minute cabinet differ from a 90-minute cabinet?**

The difference is how long the compartment stays isolated from a fire: type 30 protects the contents for half an hour, type 90 for an hour and a half. Both classes are defined by the same standard, EN 14470-1. The extra sixty minutes are a margin for evacuation and firefighting. For small quantities of solvents type 30 is usually enough; for larger stocks, type 90 is the choice.

**Is there an under-worktop cabinet in the 30-minute class?**

No, the 30-minute class includes only floor-standing cabinets with heights from 1947 to 1968 mm. For under-worktop use there is the K-UB-90 from the 90-minute class: it is 601 mm high and 1102 or 1402 mm wide. It is chosen when flammable liquids need to be kept right at the workstation and the room has no space for a tall cabinet.

**Can a fire-resistant cabinet replace a ventilated cabinet?**

No, they are two separate solutions. A ventilated chemical cabinet removes vapours but has no thermal insulation and no fire resistance class. A type 30 cabinet protects flammable liquids from fire and, when connected to extraction, also removes their vapours. For volatile, non-flammable reagents a ventilated cabinet is usually sufficient, as we explain in the article [ventilated cabinets for laboratory reagents](https://www.renggli.pl/en/blog/ventilated-reagent-cabinet-laboratory).

**How can you tell that a cabinet really is rated for 30 minutes?**

By its type designation under EN 14470-1 and the test documentation, not by its trade name. The standard requires the complete cabinet to be tested in a test furnace, and the result is confirmed by a document from an independent body. A material's reaction to fire class, for example B-s1,d0 to EN 13501-1, describes only how the board behaves and says nothing about how long the cabinet will protect its contents.