Laboratory lighting: how to choose luminaires and meet standards
Laboratory lighting is specified according to EN 12464-1: illuminance, uniformity, UGR glare, colour rendering Ra and task lighting above the countertop.

Published: Updated Reading time: 9 min read
Contents
Laboratory lighting is general room lighting combined with task lighting above the countertop, matched to the visual tasks according to PN-EN 12464-1:2022-01 (opens in a new tab) (the Polish Standard on lighting of indoor work places). The standard defines the quantity and quality of light: illuminance, uniformity, glare and colour rendering. Luminaires, power supply and laboratory furniture are planned together, because superstructures and wall cabinets decide where the light will fit.
What does EN 12464-1 require of laboratory lighting?#
EN 12464-1 sets requirements for the quantity and quality of lighting for most indoor workplaces, including laboratory workstations. The current Polish edition is PN-EN 12464-1:2022-01, which, according to the standard's entry in the PKN catalogue (opens in a new tab), adopts EN 12464-1:2021 and replaces the 2012 edition.
The parameters are matched to the type of workstation and activity, not to the whole room as a single zone. The task area on the countertop has higher requirements than its immediate surroundings. According to the CIOP-PIB guidelines (opens in a new tab) (Poland's Central Institute for Labour Protection), prepared on the basis of the 2012 edition, the requirements of the standard are taken into account in the lighting design and verified in an existing installation.
The obligation comes from occupational health and safety law. The regulation on general occupational health and safety rules (opens in a new tab) requires, in § 26, electric lighting in work rooms with parameters that comply with Polish Standards. In § 28 it requires emergency lighting where a lighting failure would endanger the life or health of workers, and in § 27 gradual adaptation of vision when leaving a darkroom.
How does laboratory lighting differ from office lighting?#
Laboratory lighting has to make it possible to read the scale on a burette, judge the shade of a solution and notice a precipitate as it forms, whereas in an office the task is usually high-contrast text. In titration, the moment the indicator changes colour decides the result, so poor light can be as much a source of error as an inaccurate vessel.
An underlit countertop rarely looks like a problem straight away. The worker leans over the vessel, brings their eyes closer to the scale and strains their eyes throughout the shift, while the risk of a misreading grows.
A laboratory is also hard on the luminaires themselves. Reagent vapours, moisture and frequent cleaning of surfaces speed up wear. That is why luminaires are chosen with a chemical-resistant housing and a cover that keeps vapours from settling directly on the light source. Light-sensitive reagents are stored out of reach of intense task lighting, which has to be taken into account when positioning cabinets.
How many lux does a laboratory need?#
For practical classrooms and laboratories in educational buildings, EN 12464-1 requires 500 lx, as stated in the summary by the County Sanitary and Epidemiological Station in Krasnystaw (opens in a new tab). The standard lists laboratories in other sectors in its tables by type of interior and task, so the design starts with a list of visual tasks at each workstation. The area surrounding the task may have a lower illuminance: with 500 lx on the countertop, it is 300 lx according to the CIOP-PIB guidelines (opens in a new tab).
| Parameter | What it means | Value from an open source |
|---|---|---|
| Illuminance Em (lx) | Average illuminance in the task area, maintained throughout the life of the installation | 500 lx in laboratories in educational buildings (PSSE (opens in a new tab)) |
| Illuminance of the surrounding area (lx) | Band around the task area; too large a difference in illuminance tires the eyes | 300 lx with 500 lx in the task area (CIOP-PIB (opens in a new tab)) |
| Uniformity Uo | Ratio of the minimum to the average illuminance; a low value means dark spots on the countertop | Minimum from 0.40 to 0.70 depending on the task, at least 0.40 in the surrounding area (CIOP-PIB (opens in a new tab)) |
| Glare UGR | Unified glare rating for discomfort glare from luminaires; the standard gives a limiting value for each task | The more demanding the task, the stricter the glare limit (CIOP-PIB (opens in a new tab)); the limiting value is given in the standard's table for the task |
| Colour rendering Ra | How faithfully the light renders the colours of objects and solutions | At least 80, at least 90 where colour is checked (CIOP-PIB (opens in a new tab)) |
| Light colour | Colour temperature of the source: warm, neutral or cool | Neutral from 300 to 750 lx, cool above 750 lx (CIOP-PIB (opens in a new tab)) |
Judging the colour of a solution during titration and in diagnostics is a task in which colour discrimination is essential. Such workstations need light sources from the highest colour rendering class given in the table.
When does a laboratory need task lighting?#
Task lighting (a luminaire mounted above the countertop) is used where the task needs more than 500 lx: for such workstations, the CIOP-PIB guidelines (opens in a new tab) recommend local supplementary lighting. Ceiling light alone is rarely enough for precision work, because a worker leaning forward casts a shadow right onto the task area.
Combining general lighting with task lighting means the illuminance of the whole room does not have to be raised to the level of the most demanding task. Each workstation can then be switched on and adjusted separately, depending on the work being done.
A local luminaire should have an adjustable light-emitting part, should not cause glare and should not get hot enough to burn the skin on accidental contact. Its colour rendering index should be at least 80, according to CIOP-PIB (opens in a new tab). Among the parameters to assess, the same guidelines list flicker and the stroboscopic effect, which with centrifuges and stirrers can make a rotating part look stationary.
How can glare and reflections from the countertop be limited in a laboratory?#
Glare is limited by the position of the luminaires relative to the workstations, by light-diffusing covers and by matt work surfaces. Direct glare comes from a luminaire visible in the field of view, while reflected glare occurs when light bounces off a glossy surface straight into the eyes.
To counter reflected glare, the CIOP-PIB guidelines (opens in a new tab) recommend matt surfaces and, where that is not possible, changing the angle at which the light falls, especially with local luminaires. A reflection on the countertop makes it harder to read the meniscus in a glass vessel, because the edge of the liquid is no longer clear.
The finish of laboratory countertops is agreed with the lighting design before the luminaires are installed. Once they are in place, changing the light layout is much harder than on a drawing.
What lighting is needed in a fume hood and in an explosion hazard zone?#
A fume hood chamber needs even, shadow-free light across the whole work surface, while the chamber stays sealed and the exhaust airflow is not disturbed. The chamber luminaire is part of the fume hood equipment, so its design is checked in the fume hood quotation, not in the ceiling luminaire design.
In rooms where flammable vapours can form, luminaires are selected for the explosion hazard zone. Under the rozporządzenie o atmosferze wybuchowej w miejscu pracy (opens in a new tab) (Polish regulation on explosive atmospheres in the workplace), the employer divides areas at risk of explosion into zones and selects equipment of the category assigned to each zone. A luminaire that is not suited to the zone can become an ignition source, as described in the article on how to ensure safety in a chemical laboratory.
In microbiology laboratories, cleanrooms and glassware washing rooms, surfaces are disinfected frequently. What counts there is the tightness of the luminaire housing (IP rating) and a material resistant to vapours, such as stainless steel or toughened glass.
What should you check when ordering laboratory furniture for the lighting?#
Furniture and lighting are coordinated at the stage when the laboratory design is drawn up, because that is when you can see how much space remains for a luminaire above the countertop and where the power supply will run. The points to agree on are the height of the wall cabinets, the position of the luminaire, cable routing away from water and gas, and switches within reach of a person standing at the countertop.
We manufacture custom laboratory furniture at our factory in Białystok, in the RL1 to RL7 systems and in individual designs. A laboratory superstructure is a frame above the countertop that carries the services (sockets, gas, water and vacuum valves), with reagent shelves above them. In the RL3 system, electrical installations run in ducts made of sheet metal, plastic or aluminium.
The laboratory fume hoods we supply come as standard with task lighting and 230 V sockets rated IP44, and we bring the valves and switches out to an external panel. For explosion hazard zones, we offer Ex-version fume hoods. An unusual room layout or a clash with luminaires can be a reason to choose custom laboratory furniture.
Frequently asked questions#
Lighting of indoor workplaces, including laboratories, is covered by EN 12464-1, whose current Polish edition is PN-EN 12464-1:2022-01. The standard gives the illuminance, uniformity, UGR glare limit and colour rendering index Ra for individual tasks.
The Polish regulation on general occupational health and safety rules (opens in a new tab) requires, in § 26, electric lighting with parameters that comply with Polish Standards, and in § 28, emergency lighting where a lighting failure would endanger health. In explosion hazard zones, the regulation on explosive atmospheres (opens in a new tab) also applies, under which equipment is selected for the zone.
For laboratories in educational buildings, EN 12464-1 requires 500 lx, according to the PSSE summary from Krasnystaw (opens in a new tab). For workstations where the task needs more than 500 lx, CIOP-PIB (opens in a new tab) recommends supplementary lighting from a local luminaire.
It is a luminaire above the countertop that raises the lighting of the task area above the general lighting level and removes the shadow cast by a worker leaning forward. Its position and power supply are planned together with the superstructures and wall cabinets.
The design starts with a list of visual tasks at each workstation, because they determine the values taken from EN 12464-1. General lighting is combined with task lighting, light sources with a high Ra index are chosen for colour assessment, and work surfaces are chosen with a matt finish.